Product Description
Mode of Operation:
Upon reaching the pre-set interval time for defrost to occur, the ICM550 will enter the defrost cycle which will turn off the fan and turn on the backup heating source. The ICM550 will remain in defrost for the set defrost time. At the end of the set defrost time, the unit will return to normal operation until the next pre-set interval for defrost occurs.
Specifications:
Electrical Rating Voltage: 120-240VAC Frequency: 60 Hz
Output Type: Relay Form: SPDT, SPST Rating: Normally closed: 30A @ 240 VAC, Normally open: 40A @ 240 VAC
Timing Minimum defrost time: 15 minutes Maximum defrost time: 23 hours 45 minutes Terminate defrost: Defrost can be terminated by shorting “X to N”
Status LED: Defrost mode (Red LED) and Refrigeration mode (Green LED)
• ICM550 defrost control module and Bracket mount
• Installation guide
• Terminal block & wiring diagram label sheet
• #8 x 1/2” sheet metal screws and #6 x 1/2” hex head screws
• Replaces - Grasslin: 010-0011B, DT040, DT140, DTAV40, DTMV, DTSX. Paragon: 8041, 8045, 8047, 8141, 8143, 8145, 8245, 8247. Precision: 6041, 6045, 6047, 6141, 6145